When you would like to secure affordable procurement options for Eaton Corporation part number JC1-A8-A-5-10, do not hesitate to take advantage of the Request for Quote (RFQ) form on this page. As you complete this form, be sure to offer us important details like your target price and expected fulfillment timeframe, as well as information for contacting you with our response. Within 15 minutes of receiving and reviewing your submission, a member of our staff will reach out to you to present a tailored solution on Eaton Corporation part number JC1-A8-A-5-10 for your comparisons.
| NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
|---|---|---|---|---|---|---|
| 5925-01-127-9398 Item PartTypeName: CIRCUIT BREAKER | 5925 | 011279398 | P | |||
| CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
| U | ||||||
| Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
| JC1-A8-A-5-10 | 5 | 9 | 3 |
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | BODY STYLE | SINGLE POLE TYPE |
| ADAQ | BODY LENGTH | 1.968 INCHES MINIMUM AND 2.032 INCHES MAXIMUM |
| ADAT | BODY WIDTH | 0.718 INCHES MINIMUM AND 0.782 INCHES MAXIMUM |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.528 INCHES MINIMUM AND 1.592 INCHES MAXIMUM |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.628 INCHES MINIMUM AND 1.692 INCHES MAXIMUM |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.898 INCHES MINIMUM AND 1.962 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 1 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC SINGLE LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
| CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 100.000 NOMINAL SINGLE LOCATION |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
| CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 200 PCT AND 55.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
| CTJS | UNPACKAGED UNIT WEIGHT | 1.500 OUNCES NOMINAL |
| CWJK | CASE MATERIAL | PLASTIC |
| FREQ | FREQUENCY IN HERTZ | 50.0 OR 60.0 SINGLE LOCATION |
| THSD | THREAD SERIES DESIGNATOR | UNC |
| TTQY | TERMINAL TYPE AND QUANTITY | 2 QUICK DISCONNECT,MALE |
![]() |
AS9120B and ISO 9001:2015 |
![]() |