When you would like to secure affordable procurement options for Eaton Corporation part number X0411-60-240-60C1, do not hesitate to take advantage of the Request for Quote (RFQ) form on this page. As you complete this form, be sure to offer us important details like your target price and expected fulfillment timeframe, as well as information for contacting you with our response. Within 15 minutes of receiving and reviewing your submission, a member of our staff will reach out to you to present a tailored solution on Eaton Corporation part number X0411-60-240-60C1 for your comparisons.
| NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
|---|---|---|---|---|---|---|
| 5925-00-718-7530 Item PartTypeName: CIRCUIT BREAKER | 5925 | 007187530 | 0 | P | ||
| CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
| U | A | |||||
| Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
| 421-60 | 2 | 9 | 5 |
| MRC | Criteria | Characteristic |
|---|---|---|
| ADAT | BODY WIDTH | 1.020 INCHES MINIMUM AND 1.040 INCHES MAXIMUM |
| ADTV | UNABLE TO DECODE | UNABLE TO DECODE |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.370 INCHES MINIMUM AND 4.390 INCHES MAXIMUM |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 60.0 AMPERES AC SINGLE LOCATION |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
| CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 39.000 MINIMUM AT 200 PCT AND 105.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
| CTJS | UNPACKAGED UNIT WEIGHT | 0.688 POUNDS NOMINAL |
| THSD | THREAD SERIES DESIGNATOR | UNC |
| AAQL | BODY STYLE | SINGLE POLE TYPE |
| ADAQ | BODY LENGTH | 4.740 INCHES MINIMUM AND 4.760 INCHES MAXIMUM |
| ADAU | BODY HEIGHT | 2.820 INCHES MINIMUM AND 2.840 INCHES MAXIMUM |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 1 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC SINGLE LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 175.000 MINIMUM AND 550.000 MAXIMUM SINGLE LOCATION |
| CPRQ | RESET METHOD | MANUAL |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CWJK | CASE MATERIAL | PLASTIC |
| FEAT | SPECIAL FEATURES | WITH HANDLE EXTENSION CONSTRUCTION KIT |
| FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| TTQY | TERMINAL TYPE AND QUANTITY | 2 BUS BAR |
![]() |
AS9120B and ISO 9001:2015 |
![]() |
Aviation Suppliers Association Member |
![]() |
FAA AC 0056B Accredited |
![]() |
AS 6081:2012 Certification |
![]() |
ESD S20.20-2014 Certification |
OVER 75000